“Downward airflow is effective regarding reduction of airborne bacterial counts and velocities of at least 0.3 m/s are needed to break body convection”
(c) Wang. C (2019)
Ultra-clean air is not only a result of high airflow rates – the type of airflow distribution is of critical importance in reducing cfu levels and different ventilation techniques have very different ventilation efficiency. The highest efficiency was shown by Temperature Controlled Airflow (TcAF).
(b) Nielsen, P. V. (2009)
Experiments with heated manikins indicate that downward air velocities up to 0.25 m/s preserves isothermal smoke released from above the standing manikin at head height. The thermal plume above a person has an upward velocity of approximately 0.25 m/s and down- ward air velocities of at least 0.30 m/s are needed to break the body convection.
(a) Whyte, W., Shaw, B. H. & Barnes, R. (1973)
In 1973 Whyte et al investigated the efficiency of unidirectional air-flow in operating theaters where both horizontal and vertical flow were evaluated. Conventional surgical clothing was used and the investigation concluded that vertical airflow velocities in the region 0.3-0.4 m/s is enough to keep the mean value of airborne bacterial counts measured at the wound site below the limit for ultraclean surgery. Furthermore, it was concluded that the vertical airflow was about 11 times more efficient regarding airborne bacteria count than horizontal.
Get the full list of scientific evidence
An extensive list of all scientific literature – in total 45 pieces – that supports Opragon is available on request using the download button below.
We can tell you more
The Avidicare team is open to presentation and in-depth discussion on how the Opragon system can make a difference for both patients and hospital staff.